UPS Battery Backup Time Calculator

How long your UPS or inverter battery will keep fans, lights, a router or a fridge running during load shedding.

Rules last checked 25 October 2026Every step shown

Your numbers are saved in this browser.
watts

Add up what stays on: a fan is 60 to 80 W, an LED light 10 to 20 W, a router 10 W, a TV 80 to 120 W, a fridge about 150 W.

Ah

For batteries wired in series or parallel; the total stored energy is what counts.

%

Backup time

3 h 24 min

Energy stored
2,400 Wh
Usable energy
1,020 Wh

A 200 Ah 12 V lead-acid or tubular battery runs 300 W for about 3 h 24 min.

How it's worked out

  1. Stored200 Ah × 12 V × 12,400 Wh
  2. Usable× 50% depth of discharge × 85% inverter efficiency1,020 Wh
  3. Backup time1,020 Wh ÷ 300 W3 h 24 min
  • Lead-acid batteries last longer when drained only halfway, so this uses 50%. Old batteries hold less.
  • Fridges and motors draw more when they start, and a UPS also charges the battery from mains; real backup is often a little shorter.

The formula

Backup hours = Ah × volts × batteries × depth of discharge × inverter efficiency ÷ load watts

Worked example

200 Ah × 12 V = 2,400 Wh stored. Using half of it at 85% efficiency gives 1,020 Wh, which runs a 300 W load for about 3 hours 24 minutes.

Questions people ask

How long will a 200 Ah battery last?

A 200 Ah 12 V tubular battery running 300 W lasts about 3 hours 24 minutes, draining it halfway with an 85% efficient inverter.

Why only use half the battery?

Lead-acid and tubular batteries wear out much faster if drained fully, so 50% is the usual limit. Lithium batteries can safely use about 90%.

How do I work out my load?

Add up what stays on: a fan is 60 to 80 W (a DC inverter fan about 30 W), an LED light 10 to 20 W, a router 10 W, a TV 80 to 120 W.

About this calculator

Formula and rules last checked 25 October 2026Written and tested by the CalculatorDex teamReport a problem